What exactly is RF power?
Two transmitters operate at 2.45 GHz. Does that mean they transmit the same power?
No. Both signals complete 2.45 billion cycles per second, but their voltage amplitudes can differ. One can swing between larger positive and negative voltages than the other. Frequency tells us how fast the voltage oscillates; amplitude tells us how large that oscillation is.
To see why amplitude matters, suppose both outputs are sine waves centered on 0 V, each connected to an identical ideal 50 Ω resistor. Across the same resistance, a larger voltage drives a larger current, transferring more energy to the resistor each second. RF power is the rate at which an RF signal transfers energy.
Power is measured in watts (W), and energy in joules (J). One watt means one joule transferred each second. A milliwatt (mW) is one thousandth of a watt, so 10 mW means 0.010 joules transferred per second.
Doubling the voltage across the same resistor doubles the current too. Power depends on their product, so the average power becomes four times larger. For the same waveform and resistance, average power is proportional to voltage amplitude squared.
For our two 2.45 GHz sine waves, a peak voltage of 1 V across the 50 Ω load gives 10 mW average power; a peak voltage of 2 V gives 40 mW. These averages cover complete cycles. The second signal transfers four times as much energy each second, even though its frequency is unchanged. The waveform and load matter: voltage amplitude alone does not specify power.
Leaving either transmitter on for longer delivers more energy without changing its average power. Over a stated interval, average power is the transferred energy divided by elapsed time:
Milli also applies to energy: 1 millijoule (mJ) is 0.001 J. Micro (µ) means one millionth; pico (p) means one trillionth. We will use these prefixes for smaller powers and energies throughout the lesson.
Think about itA source delivers 10 mW average power over two seconds. How much energy does it deliver?
. Frequency never enters this calculation. Keeping the same average power for twice as long delivers twice as much energy.
Where does the power go?
In our resistor example, the delivered energy becomes heat. A transmitter can instead send energy through a cable to an antenna, which releases energy as electromagnetic waves. RF power carried along the cable is called conducted power; the part that leaves the antenna as waves is radiated power.
The antenna may not radiate all the power arriving from the cable. Some can be reflected back along the cable at the connection to the antenna, called the antenna feed.
The power arriving at the feed is incident power; the power returning along the cable is reflected power. Subtract that returned power from the arriving power to find the accepted power: the net amount entering the antenna.
Some accepted power heats the antenna; the rest is radiated.
Where the antenna’s power goes
At the antenna feed
10 mW arrives
Inside the antenna
8 mW is accepted
The original 10 mW splits into 2 mW reflected, 1 mW of antenna heating and 7 mW radiated. The accepted 8 mW includes both the heating and the radiation.
The antenna's radiation efficiency is radiated power divided by accepted power: in the figure, 7 mW / 8 mW = 87.5%.
Before power reaches the antenna, the cable can also convert some of it to heat. A generator's output rating therefore does not tell us how much power the antenna will radiate. That rating also assumes a particular load; the source-and-load example later in this lesson shows why the connected load matters.
Power can travel through a cable or PCB trace before reaching an antenna. State where it is measured and whether you mean power arriving, accepted, or radiated.
Stating that a transmitter delivers 10 mW average power at its output connector tells us both how much power is delivered and where. Return now to the 1 V peak sine across our 50 Ω resistor. Its voltage alternates between positive and negative, yet it keeps delivering energy. Next, we will follow the voltage and current through a cycle to see how that produces the 10 mW average.
How a sinusoid delivers energy
A sine-wave voltage averages to zero. Why can it still heat a resistor?
RF Signals introduced the sine wave's changing voltage. Here, follow a 2.45 GHz sine with a 1 V peak across an ideal 50 Ω resistor. Its voltage averages to zero; the new question is what happens when we multiply it by the current.
Both directions heat the resistor
Voltage across the load
A relative to B: +0.71 V
Current (A → B): +14.1 mAFlow: A → B
Power converted to heat
Now: 10 mW
10 mW average · same two cycles in both plots
The current reverses direction, but both halves of the cycle transfer energy to the resistor. A stronger copper color shows more power being converted to heat.
Circuit and plots show the same instant.
Current heats the resistor whichever way it flows. When the voltage changes polarity, the current reverses with it. Voltage and current therefore have the same sign at each instant, so their product is positive in both halves of the cycle.
Ohm's law gives the current at each instant: voltage divided by resistance. At the positive peak, . Multiplying 1 V by 0.020 A gives 0.020 W, or 20 mW. At the negative peak, gives the same power. At a zero crossing, both readings and their product are zero.
Think about itAt one instant, the voltage across a 50 Ω resistor is −0.5 V. How much power enters the resistor?
The current is . Multiplying voltage by current gives . Both signs reverse together, so energy still enters the resistor.
For this signal, and . Here . Their product is . Instantaneous power moves from 0 to 20 mW; its average is exactly 10 mW.
The power trace has two humps during every voltage cycle. Squaring removes the sign, so the positive and negative half-cycles have the same power shape. Power therefore repeats at twice the 2.45 GHz carrier frequency, even though the carrier frequency itself did not change.
Would a higher carrier frequency deliver more energy by fitting more cycles into each second? With the same peak voltage and ideal resistance, each cycle becomes shorter and delivers less energy. Doubling the frequency gives twice as many cycles, each carrying half as much energy. The average power stays at 10 mW.
Go deeperWhy the average is exactly half the peak
To average a changing power, add its energy contributions over a complete cycle and divide by the cycle's duration. An integral is the continuous version of that addition:
A trigonometric identity lets us rewrite this signal's instantaneous power as:
This is a constant 10 mW minus an oscillating cosine term. The cosine term averages to zero over a complete cycle, leaving 10 mW average power. At 2.45 GHz, one carrier cycle lasts about 408 ps and transfers about 4.08 pJ.
An ideal resistor only absorbs energy. Some loads temporarily store energy and then send it back toward the source. During that return, instantaneous power is negative: energy is leaving the load. The next module, Impedance & Reactance, explains these energy-storing loads.
RMS: the amplitude that predicts heating
What DC voltage would heat the same resistor by the same amount?
RF Signals connected root mean square (RMS) voltage with equal heating in a resistor. Now examine how waveform shape and the measurement interval determine it. Square the changing voltage so both polarities contribute, average the squared values over a stated measurement interval, then take the square root. The result is the DC voltage that produces the same average heating in the same resistor.
For a repeating waveform, averaging over one or several complete periods gives the same RMS value. A signal that does not repeat still has an RMS value over a chosen measurement interval.
First try a simple four-step voltage that holds 0 V, +1 V, 0 V, then −1 V for equal amounts of time. Its average voltage is zero. Squaring gives 0, 1, 0, and 1 V²; their average is . The square root is about 0.707 V.
Now apply the same process to a continuously changing sine wave, including every part of the cycle.
Square. Average. Take the root.
Start with our 1 V peak sine wave, centered on zero.
Square each voltage
Squared voltage (V²)
Average squared voltage: 0.5 V²
Take the square root of the average
This gives the RMS voltage: about 0.707 V.
The square root returns the result from squared volts to volts.
What does that mean across an ideal 50 Ω resistor?
The two voltages deliver the same energy in the same time. That is the heating equivalence expressed by RMS.
For a zero-offset sine wave, the average squared voltage over complete cycles is half the squared peak. Taking the square root gives . The sine wave shown above has a 1 V peak, so its RMS voltage is about 0.707 V.
Recall that peak-to-peak voltage is the full swing: for symmetric peaks about zero, . Peak-to-peak voltage alone does not determine RMS voltage; the waveform shape matters too.
Voltage crest factor compares the largest voltage magnitude with RMS voltage. For this zero-offset sine, . It describes the voltage peaks relative to the amplitude that predicts heating.
For the stated ideal resistive load, RMS voltage and current lead directly to average power.
Think about itA sine, square wave, and triangle wave all reach ±1 V. Do they deliver equal average power to the same resistor?
No. Equal peaks do not mean equal mean-square values. How long each waveform spends near its peaks changes its RMS value and its heating.
Same peaks. Same heating?
Three waveforms centered on zero, each across a 50 Ω resistor.
The square wave stays at ±1 V. The sine and triangle spend part of each cycle closer to zero, so they deliver less average power.
Matching RMS changes the square and triangle peaks. Their shapes still differ, but all three now deliver the same 10 mW average power.
Sine
1 V peak
Voltage (V)
RMS voltage
0.707 VAverage power
10 mWSquare
1 V peak
Voltage (V)
RMS voltage
1 VAverage power
20 mWTriangle
1 V peak
Voltage (V)
RMS voltage
0.577 VAverage power
6.667 mWAll voltage plots share one scale. Every full power bar represents 20 mW.
Across the same resistor, equal RMS voltages give equal average powers—even when the waveforms have different shapes.
Go deeperRMS with a DC offset
The waveforms above are centered on zero. Adding a steady DC voltage shifts the whole waveform up or down. That steady part also heats the resistor, so it must be included when finding the total RMS voltage.
Over an interval of duration starting at , the definition is:
If the changing AC part averages to zero over that same interval, square the DC voltage and the AC RMS voltage, then add those two results: . Take the square root to obtain the total RMS voltage. For a sine wave with a DC offset, use the AC part's peak in the sine-wave shortcut, then include the DC contribution using this sum.
From voltage to power: the load and measurement point
Does “1 V RMS” tell us how much power is being delivered?
When the load voltage is known
Not by itself. The same RMS voltage produces different current and heating in different resistances. For an ideal resistor, divide the squared RMS voltage by the stated resistance.
| Known quantity | Load | Result |
|---|---|---|
| 1 V RMS | 50 Ω | 20 mW |
| 1 V RMS | 75 Ω | ≈ 13.33 mW |
| 10 mW | stated 50 Ω condition | ≈ 0.707 V RMS |
RF generators commonly specify their output voltage for a 50 Ω load. Other loads are possible; 75 Ω is common in cable-TV systems. When using the resistor-power formula, use the actual load resistance and the RMS voltage across it. The generator's voltage setting may assume a different load.
When the generator setting is fixed
To understand why the voltage measured at a generator's output depends on its load, represent the generator as an ideal voltage source followed by an internal 50 Ω resistance. With an external 50 Ω load connected, the same current passes through both equal resistances, so they share the voltage equally. To provide 1 V RMS across the load, the internal source must therefore supply 2 V RMS. The generator's 1 V setting refers to the expected load voltage.
Think about itA generator is set for 1 V RMS into 50 Ω, but an oscilloscope with a much higher input resistance shows about 2 V RMS. Is the generator necessarily wrong?
No. Replacing the 50 Ω load with the oscilloscope's much higher input resistance greatly reduces the current. Almost no voltage then drops across the internal 50 Ω resistance, so nearly the full 2 V RMS appears across the oscilloscope input. The generator's setting still describes the voltage it would deliver to a 50 Ω load.
Specified 50 Ω load
Equal resistances share the internal 2 V RMS equally: 1 V RMS across the source resistance and 1 V RMS across the load.
High-impedance input
The input resistance is much larger than 50 Ω. Very little current flows, so very little voltage is lost across the source resistance.
The generator setting describes the expected voltage across its specified load. This is an ideal circuit explanation; real probes and inputs also have frequency-dependent behavior. is the symbol for impedance.
The diagram's nearly 2 V RMS oscilloscope reading assumes the input draws very little current, leaving almost no voltage drop across the generator's internal resistance. A real oscilloscope and its probe can draw more current at RF because they also store and release charge as the voltage changes. This changes the voltage at the generator's output. Impedance & Reactance explains how this happens.
The earlier 50 Ω and 75 Ω examples both assume 1 V RMS across the load. Changing the load on the generator in this diagram does not keep that voltage fixed: it changes how the internal 2 V RMS is shared between the source resistance and the load.
For example, replace the external 50 Ω load connected to the generator with a 25 Ω load. The generator's internal resistance remains 50 Ω. The smaller load draws more current through both itself and the generator's internal 50 Ω resistance. The RMS current is now . More voltage therefore drops across the internal resistance, leaving only about 0.667 V RMS across the load. The load now receives about 17.8 mW, compared with 20 mW for the 50 Ω load.
If we adjusted the generator to maintain 1 V RMS across the 25 Ω load, it would receive 40 mW. In the example above, we kept the generator unchanged and replaced the 50 Ω load with a 25 Ω load. The voltage across the load fell from 1 V RMS to about 0.667 V RMS.
With this generator's internal voltage held fixed, a 50 Ω load receives the most power: 20 mW. A higher or lower load resistance receives less. This maximum deliverable power is the source's available power. It describes the source under the stated load condition; cable losses, reflection and antenna heating can still reduce the power that is eventually radiated.
Where is the measurement made?
Now consider a separate cause of a changed power reading. A cable turns some signal energy into heat, so less power reaches its output than enters its input. A reading therefore needs a location. That location, such as the generator connector or cable output, is called the reference plane.
Where is the power measured?
Example average powers · no reflected power
A power value in watts does not assume a particular resistance. The load becomes necessary when converting it to voltage or current. Without the load condition, there is no unique voltage answer.
Watts now have physical meaning, but RF systems often span factors of millions or billions. A logarithmic language makes those ratios easier to see and combine.
Why RF engineers use decibels
What is the easiest way to follow a signal through several stages of gain and loss?
Suppose a cable reduces 10 mW to 5 mW, then an amplifier increases that 5 mW to 50 mW. The cable multiplies power by 0.5; the amplifier multiplies it by 10. Together they multiply power by five. Decibels let us calculate the same combined change by adding instead of multiplying.
If a power amplifier increases signal power by a factor of 100, its output-to-input power ratio is . A base-ten logarithm asks: what power of ten gives this ratio? Since , . For power ratios, this logarithm expresses the ratio in bels. One bel equals 10 decibels (dB), so multiplying 2 by 10 gives the amplifier's power gain of +20 dB. The power has increased 100 times; the factor of 10 converts the logarithmic value to decibels.
An attenuator that reduces signal power to one tenth has . Since , . Multiplying by 10 gives a change of −10 dB, also called a 10 dB loss. Equal dB steps therefore mean equal multiplying factors, not equal extra watts.
Think about itDoes a 3 dB loss subtract 3 mW from every signal?
No. It applies a ratio. A 3 dB loss multiplies power by about 0.501, so 10 mW becomes about 5.01 mW while 100 mW becomes about 50.1 mW. For an exact reduction to half power, the output-to-input ratio is one half, so . The negative sign indicates a decrease in power. We describe this as a 3.01 dB loss.
| Level difference | Exact power ratio | Plain-language reading |
|---|---|---|
| ≈ +3.01 dB | 2 | exactly twice the power |
| ≈ −3.01 dB | 0.5 | exactly half the power |
| +10 dB | 10 | ten times the power |
| −10 dB | 0.1 | one tenth of the power |
| +20 dB | 100 | one hundred times the power |
| −20 dB | 0.01 | one hundredth of the power |
Engineers often round the doubling or halving change to 3 dB; at that precision, say “approximately double” or “approximately half.”
To compare 20 mW with 5 mW, divide output by input: . On a calculator, is about 0.602; multiply by ten to get +6.02 dB. To convert +6.02 dB back to a power ratio, divide 6.02 by ten, then calculate 10 raised to that result: .
Before dividing the two powers, express both in watts or both in milliwatts. For an amplifier with a 10 mW input and a 1 W output, convert 1 W to 1,000 mW before dividing: . The units cancel, and gives +20 dB gain. Expressing both powers in watts would give the same ratio.
If one stage multiplies power by and the next by , the chain ratio is . Because , their decibel values add. This is a property of logarithms, not a special behavior invented for RF.
Return to the opening cable and amplifier: reducing 10 mW to 5 mW is approximately −3 dB, and increasing 5 mW to 50 mW is +10 dB. Adding gives approximately +7 dB, corresponding to five times the starting power.
dBm and dBW: absolute levels with fixed references
How can decibels describe a power level rather than just a change in power?
A gain of 10 dB tells us that power increased tenfold, but we still need the starting power to know the result. dBm compares power with a fixed 1 mW reference. A power level of +10 dBm therefore means 10 mW, and 0 dBm means 1 mW. dBW uses 1 W as its reference, so 0 dBW means 1 W.
Zero dBm still delivers power
We turn the source up and down. Watch the signal’s average power pass the fixed 1 mW reference.
Voltage across the load
One cycle at the current amplitude
Average power in the load
Averaged over the sine cycle
1 mW
0 dBm
Equal to the reference: 1 mW is 0 dBm.
Below 0 dBm, the wave is smaller than the dashed reference, but it still delivers power. The minus sign means “below 1 mW”.
Only amplitude changes; frequency and load stay fixed.
dBmReference: 1 mW
From dBm back to power
dBWReference: 1 W
From dBW to dBm
is power in watts or milliwatts; and express that same power in dBm and dBW. Use matching units when dividing by the reference power.
Think about itWhich delivers more power: −10 dBm or −30 dBm? Are either of them negative power?
−10 dBm delivers more power: it is 100 µW, while −30 dBm is 1 µW. Both are positive physical powers. A negative logarithmic level only means the power is below the 1 mW reference.
In our earlier example, the sine wave delivers 10 mW of average power to the 50 Ω resistor. That is +10 dBm or −20 dBW. Both readings describe the same power.
In dBm, we compare that power with 1 mW; in dBW, with 1 W (1,000 mW). Dividing by this larger reference makes the power ratio 1,000 times smaller. Since , we subtract 30 from the dBm value to express the same power in dBW.
Reverse the logarithm calculation to recover the power:
- Divide the dBm number by 10: .
- Use that result as a power of ten: . This means the signal power is one thousandth of the 1 mW reference.
- Multiply that ratio by 1 mW to get 0.001 mW, which is 1 µW (one microwatt).
Gain and loss through an RF chain
What reaches the load after an attenuator, amplifier, and cable?
Follow one signal from the source through an attenuator, an amplifier, and a cable. The attenuator deliberately reduces signal power, often to protect the next device from too much input power. In this example there are no reflections: the removed signal power becomes heat. The cable also turns some signal power into heat along its length.
The amplifier increases signal power by drawing energy from its DC supply. Its power gain is output signal power divided by input signal power. The gain describes how much the amplifier changes the signal; finding its output power also requires knowing its input power.
When we connect the source to the attenuator, the attenuator's input becomes the source's load. Its input circuitry receives the signal power. The amplifier's input then acts as the load for the attenuator. Each input or output connection is called a port.
At 2.45 GHz, each output in this example is connected to the 50 Ω load it is designed to drive. These connections are matched: signal power enters the next device without being reflected back at the connection in this ideal example.
Begin with the source level in dBm. Add each amplifier gain in dB and subtract each loss in dB. For example, “3 dB loss” means subtract 3 dB once. Follow the result to the next connector before applying the next block.
Think about itStarting at +10 dBm, what remains after −3 dB, +13 dB, and −2 dB?
Add the signed level changes: That is about 63.1 mW. The ideal blocks change power without changing the 2.45 GHz carrier frequency.
Where power is lost and added
Starting level
P0Source output
+10 dBm10 mWSignal enters the chain
−3 dB
P1After attenuator
+7 dBm5.01 mW4.99 mW becomes heat
+13 dB
P2After amplifier
+20 dBm100 mW94.99 mW added from DC to RF
−2 dB cable
P3At the load
+18 dBm63.1 mW36.9 mW becomes heat
Losses turn RF energy into heat; the amplifier draws extra energy from its DC supply. Its DC input must also cover amplifier heating, so 94.99 mW is the added RF power, not the total DC consumption.
About this illustration
This 2.45 GHz example assumes no reflected power and a constant amplifier gain.
Power Amplifiers (in preparation) develops efficiency and DC consumption. Two-Port Networks & S-Parameters (in preparation) explains how port conditions affect gain and connected networks.
Think about itIf the 3 dB attenuator in this chain is replaced by a 6 dB attenuator, what changes downstream?
The source stays at +10 dBm. The extra 3 dB loss lowers the power level at the attenuator output and every later connector by 3 dB. The final level becomes +15 dBm, approximately 31.6 mW, while the carrier remains at 2.45 GHz. This assumes the amplifier keeps the same gain.
Before moving the slider below, predict the gain needed to reach the target from the displayed source level after both losses. Then use the slider to check your calculation.
How much amplifier gain do we need?
Now use a 1 mW (0 dBm) source. The attenuator loses 3 dB and the cable loses 2 dB. Adjust the amplifier gain to deliver 10 mW (+10 dBm) to the load.
Change only the gain. The source and both losses stay fixed.
The gain is smaller than the combined 5 dB loss, so the load receives less power than the 1 mW source.
Ideal matched 50 Ω chain at 2.45 GHz. The amplifier provides the selected gain without compression.
These calculations assume the stated 50 Ω connections and constant amplifier gain at 2.45 GHz. With constant gain, doubling the input power in watts doubles the output power in watts. Near the amplifier's limit, the output increases by less than this. Its gain has fallen—a behavior called compression. The amplifier can also distort the waveform as it approaches this limit.
A data sheet might specify 20 dB gain at 2.45 GHz, with a 3.3 V supply and a small input signal. That value applies to those conditions: changing the supply voltage or frequency can change the gain, and a larger input may cause compression. Use gain specified near your operating conditions when calculating the output power.
A 20 dB gain describes an output-to-input ratio under stated conditions. A −30 dBm input would become −10 dBm; a 0 dBm input would become +20 dBm, provided the amplifier maintains that gain at both input levels.
Why voltage ratios use 20 log
If voltage doubles, does power merely double too?
Across the same ideal resistance, power is proportional to RMS voltage squared. Doubling voltage therefore makes four times the power. That square is where the factor of 20 comes from—it is not a separate definition to memorize.
For example, 1 V RMS across 50 Ω gives . With 2 V RMS across the same resistance, . The power ratio is four, so the change is . Since four is the voltage ratio squared, the same result is . The rule follows from for positive ratios.
Think about itAcross the same ideal resistance, RMS voltage falls to half its previous value. What happens to power and its level in dB?
Squaring the voltage ratio gives : power falls to one quarter. The level change is
| Change | Voltage ratio | Power ratio | Level difference |
|---|---|---|---|
| Double voltage | 2 | 4 | ≈ +6.02 dB |
| Double power | 2 | ≈ +3.01 dB | |
| Half voltage | 0.5 | 0.25 | ≈ −6.02 dB |
When the two resistances differ
The examples above use the same resistance for both voltages. With different resistances, the voltage ratio alone does not tell us the power ratio. One volt RMS across 50 Ω gives 20 mW; the same voltage across 100 Ω gives 10 mW. The voltage is unchanged, but doubling the resistance halves the power. To compare powers across different resistances, multiply the squared voltage ratio by . Here that resistance ratio is :
Impedance & Reactance extends these resistor examples to loads that also store and return energy. Two-Port Networks & S-Parameters (in preparation) develops power comparisons for waves travelling toward and away from RF ports.
dBc: relative to a carrier
A spur is measured at −40 dBc. What does that tell us—and what is still missing?
A spur is an unwanted frequency component. The carrier is the intended RF tone in this example. The spectrum below shows a peak for the carrier and another for the spur. Each peak's horizontal position shows its frequency, and its height shows its power level in dBm.
The suffix “c” names the reference: the carrier. A component at −40 dBc has one ten-thousandth of the carrier power under the stated measurement conditions. Its absolute power remains unknown until the carrier level is known at the same reference plane.
Record the carrier power, measurement point, and instrument settings with the dBc result. The measurement section explains how to choose the frequency range and averaging interval.
Think about itA +10 dBm carrier has a spur at −40 dBc. What is the spur in dBm and watts?
Add the relative level to the carrier level: . That is 1 µW.
Same dBc, different spur power
Keep the spur's dBc value fixed and raise the carrier level: its power rises too, while the gap between them stays the same.
The bracket measures how far the spur is below the carrier.
With the carrier at +10 dBm, a spur 40 dB below it is −30 dBm (1 µW).
Both powers refer to the same measurement location. This experiment holds the chosen dBc difference fixed; a real spur need not follow the carrier this way. The spur's frequency is illustrative.
dBc is a separation from a named carrier; dBm is a level relative to 1 mW. A −40 dBc component is −30 dBm beside a +10 dBm carrier, but −60 dBm beside a −20 dBm carrier.
Go deeperWhy does noise use dBc/Hz?
Electronic components generate random electrical fluctuations called noise, even when no transmitter is sending a message. Unlike the separate spur shown above, this noise spreads its power across a range of frequencies. If its power is spread evenly, measuring twice the frequency range collects twice the noise power.
A dBc/Hz value expresses the noise relative to the carrier per hertz. It describes how densely the noise power is spread, rather than the total collected. Noise explains how to calculate that total over a chosen frequency range.
How separate powers combine
When can separate powers be added, and when does phase matter?
Even with no incoming transmission, components in a receiver generate random electrical fluctuations called noise. Suppose two parts of the receiver contribute noise to the same output. Their fluctuations can be uncorrelated: knowing one contribution does not tell us which way the other is fluctuating.
Their instantaneous voltages still add, as in RF Signals. Sometimes the fluctuations reinforce and sometimes they oppose. For uncorrelated noise with no DC offset, the extra power from reinforcement and the reduction from opposition balance out in a sufficiently long average. Each contribution's own average heating remains, so their average powers add.
Cascaded dB values can be added because they describe ratios along one path. Separate uncorrelated contributions require another calculation: convert to milliwatts, add the powers, then convert back to dBm. Watts and milliwatts express linear power, meaning twice the number represents twice the power.
Think about itWhat is the total of two independent 0 dBm contributions at the same plane?
Each is 1 mW. The linear total is 2 mW, approximately +3.01 dBm. The answer is not 0 dBm, and writing “0 dBm + 0 dBm” as ordinary addition hides the required conversion.
Compare the three cases below: how much does a second contribution add as it becomes weaker than the first?
When does a second signal noticeably increase the total?
A stays at 1 mW (0 dBm). Only B changes between these three cases.
The contributions are uncorrelated and measured at the same load, over the same frequency range and averaging interval.
All bars use the same 0–2 mW scale.
B equals A
B: 1 mW (0 dBm)
Total level≈ +3.01 dBmB is 10 dB weaker
B: 0.1 mW (−10 dBm)
Total level≈ +0.41 dBmB is 20 dB weaker
B: 0.01 mW (−20 dBm)
Total level≈ +0.04 dBm
An equal contribution doubles the power. A contribution 10 dB weaker adds only 10% more power; at 20 dB weaker, it adds just 1%.
These examples add uncorrelated contributions. Two copies of the same tone can keep a stable phase relationship; such signals are called coherent. Their voltages can reinforce or cancel, so phase must be included before calculating their combined power.
Go deeperWhere phase enters a coherent sum
Consider two sine-wave voltages at the same frequency across one ideal resistor. Add their instantaneous voltages, square the result, and divide by the resistance to obtain instantaneous power. Averaging over complete cycles gives:
Here, and are the powers each voltage would deliver alone to that same resistance; is the relative phase between the two voltages. The last term accounts for reinforcement or cancellation. At 0°, the voltages reinforce. At 180°, equal voltages cancel at the resistor.
If each voltage alone would deliver 1 mW, equal in-phase voltages give 4 mW: doubling the voltage quadruples resistor power. Does that create energy? No. The 1 mW values describe hypothetical contributions at the load; they are not automatically the available powers of two generators connected to a combiner.
A combiner is a circuit that brings signals to a common output. It determines how much of each source signal reaches the load. A passive combiner, with no power supply of its own, cannot deliver more power than its sources provide. Two sources supplying 1 mW each can deliver at most 2 mW through it, not 4 mW. Two-Port Networks & S-Parameters (in preparation) develops the connection between generator powers and the voltages that reach a load.
Average, burst, peak, and measured power
Why can averaging the same signal over different time intervals give different powers?
Earlier, instantaneous resistor power rose and fell within each RF cycle. To see slower changes in power, average the instantaneous power over a few RF cycles at a time. Keep this interval short enough that the signal's amplitude hardly changes during it. This local average is the signal's envelope power. For a sine wave with constant amplitude, envelope power is steady. Across the same resistor, increasing the voltage amplitude increases the envelope power; decreasing it reduces the envelope power.
The voltage envelope introduced in RF Signals follows the signal's peak voltage, measured in volts. Envelope power describes the average power delivered to the load at that amplitude, measured in watts.
Choose the averaging interval
A burst is a limited on-time followed by idle time. Return to the chain's final output: 63.1 mW (+18 dBm) while the transmitter is on. Now switch that signal on for 1 ms and off for 9 ms, repeating every 10 ms. A millisecond (ms) is one thousandth of a second. The duty cycle is on-time divided by the complete repetition interval: . The on-state signal has not become weaker; it is present for less time.
A measurement gate selects which time interval contributes to a reading; it does not switch the transmitter off. A gate around the on-time measures active-state average. A gate covering complete on/off intervals measures long-term average. The highest value of the envelope power is peak envelope power (PEP).
The same burst, two averaging windows
Zoom into two cycles within the 1 ms burst
Two RF cycles · about 816 ps
Cycle average: 63.1 mW
Instantaneous power reaches 126.2 mW. Averaging over RF cycles gives the envelope power.
Across the complete burst interval
Envelope power · one 10 ms interval
Full-interval average: 6.31 mW
The zoom shows only two of the 2.45 million RF cycles within the 1 ms on-time. The burst continues beyond those 816 ps. Both plots use the same power scale; the full-interval plot shows cycle-average power, with zero watts during idle time.
A · Average over the 1 ms on-time
Active-state level: +18 dBm
B · Average over the full 10 ms
Full-interval level: +8 dBm
Both gates include the same 63.1 µJ of energy. Including the idle time spreads it over ten times the duration, so the average is one tenth as large. Choosing a gate changes the measurement, not the transmitted burst.
For an ideal rectangular on/off burst with active power and duty cycle , the long-term average across complete repetition periods is especially simple.
Think about itA burst delivers 80 mW while on and zero while idle. Its average over complete on/off intervals is 20 mW. What is its duty cycle?
Divide the full-interval average by the on-state power: . For a 10 ms repetition interval, that is 2.5 ms on and 7.5 ms off. The transmitter delivers 80 mW for one quarter of the interval and zero for the rest, giving a 20 mW average.
More time on, more average power
The signal delivers 63.1 mW while on and zero while off. Change how much of each 10 ms interval it spends on.
1 ms on · 9 ms off
- While on
- 63.1 mW +18 dBm · fixed
- Average across all 10 ms
- 6.31 mW +8 dBm
The signal delivers power for 10% of the interval, so its average is 10% of 63.1 mW: 6.31 mW. The on-state power stays unchanged.
Suppose a signal spends equal time at 1 mW and 100 mW. Its average power is , or about +17.03 dBm. Those two powers correspond to 0 dBm and +20 dBm. Averaging those dBm numbers would give +10 dBm, only 10 mW, which does not account for the energy delivered during the stronger interval.
During idle time use zero watts, not 0 dBm: 0 dBm is 1 mW. Zero watts has no finite dBm value. For unequal durations, add the energy delivered in each interval and divide by the total time.
Check the peaks as well as the average
Now use a separate example: an amplifier directly drives a matched 50 Ω load, with no intervening cable loss. Amplitude modulation, introduced in RF Signals, changes the voltage amplitude during the on-time. Here, envelope power is 20 mW for 0.5 ms, then 80 mW for 0.5 ms, followed by 9 ms at zero power.
When power varies during the on-time
Only the 1 ms on-time is plotted. The following 9 ms at zero power are outside this view.
- Peak envelope power
- 80 mWThe highest level of the envelope.
- Active-state average
- 50 mWEqual time at each level gives:
Same signal, three power readings
| What do we want to know? | Result |
|---|---|
| What is the average while transmitting? | 50 mW — average during the 1 ms on-time |
| What is the average including idle time? | 5 mW — average over the full 10 ms |
| How high does the envelope power reach? | 80 mW — peak envelope power (PEP) |
Peak-to-average power ratio (PAPR) compares the highest envelope power with the average over a stated interval. Using the 1 ms active average gives . Using the complete 10 ms average gives . The signal is unchanged; including idle time reduces the denominator.
The amplifier must reproduce the 80 mW envelope peak without compression. An amplifier that can deliver 50 mW but compresses before 80 mW will distort the higher part of this waveform, even though its full-period average is only 5 mW.
A continuous constant-amplitude sine has 0 dB envelope PAPR: its envelope peak and average are equal. This differs from the voltage crest factor in §3, which compares voltage peak with RMS voltage.
Match the instrument to the reading
Start with the quantity you want to report, then choose which frequencies and times enter the reading. Instruments measuring that same quantity at the same location should agree within their measurement uncertainty.
Frequency coverage
Suppose a signal occupies 20 MHz, but a spectrum analyzer views it through a 200 kHz filter. The filter selects only a small part of the signal's frequency range. Its width is described by resolution bandwidth (RBW). A marker reports the power passed near one frequency; that single reading cannot establish the total power of this 20 MHz-wide signal.
Channel-power integration adds the power across a selected frequency range. Set that range to include the whole wanted signal when measuring its total power, and identify any unwanted components excluded from the result. A direct reading through a filter that passes the whole signal with a flat response can also measure total power with average-power detection. Merely setting RBW equal to the signal bandwidth is insufficient: real filters roll off at their edges.
Time selection
A trigger determines when recording starts; the record length determines how much time is captured. A gate selects the part of that record to measure. For the varying-envelope example, a gate spanning the complete 1 ms on-time must include both the 20 mW and 80 mW intervals to return 50 mW. To measure the 5 mW full-period average, include one or more complete 10 ms repetition intervals, with their idle time.
Measurement response
The detector is the method the instrument uses to turn the signal into a reading. Average-power detection must average power, rather than dBm values, over the chosen gate. To measure PEP, use a peak-capable sensor or recording mode whose response is fast enough to resolve the envelope peak. A sensor that averages across the entire burst may report the average correctly while hiding that peak.
Input conditions
Establish the load presented by the instrument and account for any cable or attenuator between it and the named measurement point. Excessive input power can distort the instrument's response; weak signals can be buried in its own noise. Input attenuation reduces the level reaching the analyzer's internal circuits, so select it to avoid overload while keeping the wanted signal distinguishable from instrument noise. Check the permitted input rating too: a display setting alone does not make an excessive input safe.
| Instrument view | What it helps you see | What to establish |
|---|---|---|
| Power meter | Average power at its input; some sensors also resolve bursts and peaks | Whether the sensor measures the required average or peak, and which interval it includes |
| Spectrum analyzer | How power is distributed with frequency | Which frequency range is integrated, whether detection measures average or peak power, and which time interval is included |
| Time-domain instrument | How voltage or envelope changes with time | Whether the input load and recording speed preserve the waveform, and which interval is used in the calculation |
Spectrum & Signal Analysis (in preparation) explains how to choose resolution bandwidth, detectors, averaging, and input levels for a measurement.
Apply it: calculate and report RF power
Can you choose the calculation at each step, then describe exactly what the results mean?
Use this new case to connect voltage, gain and loss, relative power, and timing. During transmission, a 915 MHz zero-offset sine measures 0.4 V peak-to-peak across the attenuator's matched 50 Ω input at P0. This is the actual load voltage, not an unloaded generator setting.
- The signal passes through a 3 dB attenuator, an amplifier with 20 dB gain, and a cable with 7 dB loss.
- All connections are matched to 50 Ω, and the amplifier maintains the stated gain at 915 MHz.
- At the final load, P3, a measured spur is −30 dBc during the on-time, relative to the carrier there.
- The carrier transmits for 3 ms every 12 ms, with zero carrier power during the 9 ms idle time.
Where are P0, P1, P2 and P3?
Calculate the following before opening the solution. Keep full precision through each calculation and round only the displayed results. Report the carrier and spur separately.
- Find the source peak and RMS voltages, then its on-time power at P0 in milliwatts and dBm.
- Find the on-time carrier power at P1, P2, and P3 in milliwatts and dBm.
- Find the on-time spur power at P3 in microwatts and dBm.
- Find the duty cycle and full-period carrier average at P3 in milliwatts and dBm.
- Write a measurement report. Which conditions are given, and which instrument details still need recording?
Reveal the complete solution
Convert the measured voltage at P0
The sine is centered on zero, so its peak is half the peak-to-peak voltage. Convert that peak to RMS before using the 50 Ω load:
Follow the carrier through the chain
Subtract 3 dB, add 20 dB, then subtract 7 dB. The net change is +10 dB, so P3 has ten times the power at P0. These carrier results exclude the separately reported spur.
| Connection | Power | Power level |
|---|---|---|
| P0 · source output | 0.4 mW | ≈ −3.98 dBm |
| P1 · after 3 dB loss | ≈ 0.2005 mW | ≈ −6.98 dBm |
| P2 · after 20 dB gain | ≈ 20.05 mW | ≈ +13.02 dBm |
| P3 · after 7 dB loss | 4 mW | ≈ +6.02 dBm |
For example, P1 is ; use that unrounded result for the following stages. For the final power, the combined change gives mW directly.
Calculate the spur and the full-period average
−30 dBc means one thousandth of the carrier power at the same point during the same on-time. At P3:
The carrier is active for one quarter of each complete repetition interval. Average its energy over all 12 ms, including zero carrier power while idle:
Report the location, quantity, and interval
At the matched 50 Ω load after the cable (P3), the 915 MHz carrier delivers 4 mW (approximately +6.02 dBm), averaged over RF cycles during each 3 ms on-time. With 9 ms of zero carrier power while idle, its average over each complete 12 ms repetition interval is 1 mW (0 dBm). The spur measured at P3 during the same on-time is 4 µW (approximately −23.98 dBm), or −30 dBc relative to the carrier. The carrier results exclude this spur.
In a real measurement, also record the instrument and measurement mode, the included frequency range, and the gate and averaging settings. For the full-period carrier result, include the wanted burst signal's bandwidth while excluding the separately reported spur; one narrow marker at 915 MHz does not establish that total. Those settings are not supplied in this case.
Choose the calculation you need
- Voltage to power: establish RMS voltage across the actual resistive load, then use . A peak-voltage shortcut also needs the waveform shape.
- A chain of gains and losses: start with a power level in dBm, add gains in dB, and subtract losses in dB under the stated matching and gain conditions.
- Separate uncorrelated contributions: convert to milliwatts, add, then convert back to dBm. Coherent signals also require phase and circuit information.
- A changing power over time: add the energy delivered in each interval and divide by total time. With zero idle power, multiply duty cycle by the average power during the on-time; for a flat burst, this is its constant on-state power.
- A measurement report: name the location and load, defined power quantity, included frequencies, time interval, and instrument mode and settings.
Apply this with your own values: convert between watts, dBm, and sinusoidal voltage, keeping the load resistance explicit.
Check your understanding
Answer each question in your own words, then reveal the model answer.
0116 mW arrives at an antenna feed; 4 mW reflects and 3 mW heats the antenna. How much power is accepted and radiated, and what is its radiation efficiency?
Model answerThe antenna accepts 16 − 4 = 12 mW and radiates 12 − 3 = 9 mW. Radiation efficiency compares radiated with accepted power: 9/12 = 75%. The 4 mW reflected, 3 mW heating loss, and 9 mW radiated account for all 16 mW arriving at the feed.
02An ideal 3 V RMS source with 50 Ω series resistance delivers 2 V RMS across a 100 Ω load. Replace that load with 50 Ω without changing the source. Why can’t you reuse the 2 V reading, and what power reaches the new load?
Model answerChanging the load changes the current and the voltage division. With two equal 50 Ω resistances, the new load gets half the internal source voltage: 1.5 V RMS. Its power is (1.5 V)² / 50 Ω = 0.045 W = 45 mW. The former 2 V reading described a different load.
03Compare 0.4 V RMS across 50 Ω with 0.8 V RMS across 200 Ω. What is the power difference in dB, and why doesn’t doubled voltage settle the answer?
Model answerBoth deliver 3.2 mW: 0.4²/50 = 0.0032 W and 0.8²/200 = 0.0032 W. The power ratio is one, so the difference is 0 dB. The fourfold resistance cancels the squared voltage increase; the 20 log voltage shortcut alone requires equal resistances.
04A signal spends equal time at 1 mW and 9 mW. What is its average power in milliwatts and dBm? Explain using energy why averaging the dBm readings directly gives the wrong result.
Model answerEqual durations contribute energy in proportion to their powers, giving (1 + 9)/2 = 5 mW, approximately +6.99 dBm. Average power must account for that total energy divided by total time. Averaging logarithmic readings instead would give about +4.77 dBm, or 3 mW, which does not account for all the delivered energy.
05A desired amplifier-output waveform needs 10 mW active average and 40 mW envelope peak. The amplifier directly drives the matched load and remains linear only to 30 mW. Will reducing duty cycle from 25% to 5%, with zero power while idle, let it reproduce the waveform?
Model answerNo. The desired full-period average falls from 2.5 mW to 0.5 mW, but each active burst still requires a 40 mW peak. That exceeds the amplifier’s 30 mW linear limit, so the peaks are distorted. These averages describe the desired waveform, not the actual compressed output.
06Two generators can each supply 1 mW to their specified loads. Does that establish the power delivered through a combiner to one load? What else must you know?
Model answerNo. You need the signals’ phase relationship, the combining circuit, its load conditions, and its losses. The separate generator ratings do not specify the voltages that actually reach the common load. A passive combiner cannot deliver more power than the sources provide; it does not turn two 1 mW supplies into 4 mW.
07Turn “RF power: −6 dBm” into a measurement-report template. Identify what is missing without inventing it.
Model answerAt [location], with [load condition], the [defined quantity, such as carrier average power] is −6 dBm over [included frequency range], measured during [time interval or gate], using [instrument and measurement mode, including averaging settings]. All bracketed information is missing. The number alone cannot establish whether it describes a carrier, a whole channel, an on-time average, or another quantity.
Free practice / No account needed
Try 6 quick questions.
Check your reasoning before moving on. This practice stays on this page and does not count toward a certificate.
Finished all five modules? Explore practice and supervised certification →
References and further reading
The lesson synthesizes the sources below. Antenna-Theory informed the intuitive teaching approach; standards and measurement references guided notation, definitions, and caveats.
Standards and notation
RF power measurement
- Keysight: Fundamentals of RF and Microwave Power Measurements, Part 1
- Keysight: Fundamentals of RF and Microwave Power Measurements, Part 2
- Rohde & Schwarz: RF Fundamentals, transmission characteristics and signal levels
- Rohde & Schwarz: Voltage and Power Measurements
- Rohde & Schwarz: Fundamentals of RF Power Sensors
- Analog Devices: Measurement and Control of RF Power, Part I
- Analog Devices: dBm, dBmV, and dBµV conversions
- NI: Optimizing basic power measurements on vector signal analyzers
Something unclear or incorrect? Suggest a correction